• Safety pressure switches for heating systems applications
• The devices automatically stop the heat generator when a pre-set water pressure limit is reached
• Reset is exclusively manual by pressing the manual reset key after the pressure has returned by at least 0.4 bar within the shutoff value
• External graduated scale on the instrument
• Double normally closed electric contact (PMR/5EU) or normally open contact (LPR/5) in brass alloy with Ag-Ni coating
• Terminals with M4 screws and 8x8 mm pressure dice
• NBR rubber membrane with textile insert
• ¼" F hydraulic connection made of galvanised steel
• Standard protection degree IP 44
• Tear resistant cable clamps
• Maximum fluid temperature: 110°C
• Max ambient temperature 55°C
APPLICATIONS: Pressure switches for heating systems, Pressure switches for firefighting systems


| TECHNICAL DATA | PMR/5 | 
| Electrical contact | N.C | 
| Pressure range | 1-5 bar | 
| Factory settings | 3 bar | 
| Rated current | 16(10) A | 
| Rated voltage | 250 V | 
| Max fluid temperature | 110°C | 
| TECHNICAL DATA | PMR/10 | 
| Electric contact | N.C | 
| Pressure range | 1-9 bar | 
| Factory settings | 5 bar | 
| Rated current | 16(10) A | 
| Rated voltage | 250 V | 
| Max fluid temperature | 80°C | 
 ITALTECNICA
  		  		
  		  		  6157Kb
  
  		ITALTECNICA
  		  		
  		  		  6157Kb
     Regulaciona Tehnika 2012
  		  		
  		  		  4631Kb
  
  		Regulaciona Tehnika 2012
  		  		
  		  		  4631Kb
    
AVIT d.o.o.  •   Novosadski put 62,  21203 Veternik
Tel: +381 21 64-10-160  •  +381 21 820-416  •  381 21 820-681  •  Fax: +381 21 64-10-159
AVIT d.o.o.  •   Bulevar Arsenija Čarnojevića 70, 11070 Novi Beograd
Tel/Fax: +381 11 3122-559
Sva prava zadržana. Tehnički podaci, slike i crteži objavljeni na našim stranicama su isključivo informativnog karaktera. Slike na sajtu su ilustracije. O tačnim podacima se možete informisati kod naših inženjera. Zadržavamo pravo promene podataka.
Copyright © 2010 Avit d.o.o.